Improvments In Conveyor Belt Fire Suppression Systems For U.S. Coal Mines; Preprint
-
1/1/2010
Details:
-
Personal Author:
-
Description:Current regulations for fire suppression systems in underground coal mines to protect conveyor belt installations have been in place since the Coal Mine Health and Safety Act of 1969 was enacted. Over time, the coal conveyer equipment being used and ventilation conditions underground have changed significantly, particularly the width of the conveyor belts and the use of belt air at the face. The effect of these new conditions on the effectiveness of suppression systems during a fire is not known. The National Institute of Occupational Safety and Health (NIOSH) conducted a study to evaluate the effect of air velocity, water sprinkler activation temperature, and a limited water application time on the effectiveness of water sprinkler fire suppression systems to extinguish large-scale conveyor belt fires. The fire tests were conducted using both new and used 1.8-m-wide, fire-resistant rubber belt that met the Mine Safety and Health Administration (MSHA) flame resistant requirement specified in Title 30, Code of Federal Regulations, part 18, section 18.65 (also known as the 2G test). Tests were conducted using standard response sprinklers with activation temperatures of 68 °C and 141 °C at air velocities of 0.5 and 5.1 m/s. Two tests were conducted at both air velocities for each sprinkler activation temperature, one using a new belt and one with a used belt. The results showed that the suppression system was able to suppress the fires in ten minutes to the point that a miner could extinguish it with a fire hose. However, in several of the tests, the fire reestablished itself a few minutes after the sprinkler water supply was cut off and quickly grew out of control. This report discusses the large scale experimental configuration, the installation specifications of the fire suppression system, and the results and conclusions regarding the effect of air velocity, sprinkler activation temperature, and limited water application on the suppression system performance.
-
Subjects:
-
Collection(s):
-
Main Document Checksum:
-
Download URL:
-
File Type: