FACE Fatal Facts: Electrocution Hazard from Overhead Lighting Systems

File Language:
English


Details

  • Corporate Authors:
  • Description:
    On October 5, 2004, a maintenance worker at an assistedliving facility in Washington State was electrocuted while attempting to change a metal halide light bulb. The bulb broke off in the fixture when the victim first tried unscrewing the bulb. After this, he studied the "as built" facility wiring plans and shut off the electrical breaker to the lights in the area. The victim turned the light switch off and placed tape over the switch. He then went up above the suspended ceiling where he removed the can-light housing containing the bulb. At this point the victim was likely electrocuted when he touched the energized bulb filament while grounding himself to the metal housing or ceiling grid. He was trying to remove the bulb stem with metal pliers. The broken light was wired to a separate emergency circuit designed to maintain lighting in the event of loss of electricity. Metal halide and other high intensity bulbs frequently used in commercial and high occupancy buildings use higher voltages and current than common household light fixtures. These systems present hazards that licensed electricians are trained to recognize, but that others may not. These systems contain capacitors that store energy and generate high temperatures that can make it difficult to remove old bulbs. However, hanging a light bulb may normally be done safely by maintenance personnel if done with care. But other work, including removing abroken light bulb, should be performed by a licensed electrician familiar with the type of system installed. How to Prevent Similar Incidents: The following recommendations could help prevent a similar incident: 1. Only qualified electricians should work on electrical systems. Employers should assure that other workers are specifically instructed not to perform any type of work on electrical circuits. 2. Electrical systems and components must be tested to assure they are de-energized before performing work. Light switches and breakers for components cannot be assumed. If you can't test, let it rest. 3. Proper lock-out/tag-out procedures should be used when work is done on any system that may contain electrical energy. 4. Tools for de-energizing circuits should not be supplied to untrained personnel. Make sure appropriate testing devices are used and that personnel are knowledgeable and trained in their safe operation. In most cases it is recommended that a licensed electrician perform the testing. 5. One should not rely on "as built" electrical drawings to determine current electrical system design and operation. Systems must be verified in place by testing and tracing the actual configuration. 6. The accident prevention program for facilities with these types of lighting systems should describe this electrocution hazard for maintenance personnel. 7. Electrical breakers should be clearly labeled to indicate their action location and purpose. Description provided by NIOSH
  • Subjects:
  • Keywords:
  • Series:
  • Document Type:
  • Funding:
  • Genre:
  • Place as Subject:
  • CIO:
  • Topic:
  • Location:
  • Pages in Document:
    1
  • NIOSHTIC Number:
    nn:20051301
  • Citation:
    Olympia, WA: Washington State Department of Labor and Industries, 47-13-2007, 2007 May; :1
  • Contact Point Address:
    SHARP Program, Washington Department of Labor & Industries, PO Box 44330, Olympia, WA 98504-4330
  • Email:
    SHARP@Lni.wa.gov
  • Federal Fiscal Year:
    2007
  • Performing Organization:
    Washington State Department of Labor and Industries
  • Peer Reviewed:
    False
  • Start Date:
    20050701
  • Source Full Name:
    Fatal facts: electrocution hazard from overhead lighting systems
  • End Date:
    20260630
  • Download URL:
  • File Type:
    Filetype[PDF - 151.25 KB]
  • Collection(s):
  • Main Document Checksum:
    urn:sha-512:6e48e842c4b968e7343a07ace4a4a70850d679ee26c0407bd397521936db84bb242bf16b474c95c660dcaf755a77d16f6a6d7a8028cce0add28457c0aa0c644c
File Language:
English
ON THIS PAGE
 Was this page helpful?
 Found an issue?
Send us an email at:
CDC STACKS serves as an archival repository of CDC-published products including scientific findings, journal articles, guidelines, recommendations, or other public health information authored or co-authored by CDC or funded partners.

As a repository, CDC STACKS retains documents in their original published format to ensure public access to scientific information.