Development of a Method for Bacteria and Virus Recovery from Heating, Ventilation, and Air Conditioning (HVAC) Filters
-
2006/09/06
-
Details
-
Personal Author:Anantharaman S ; Farnsworth JE ; Goyal SM ; Kim SW ; Kuehn TH ; Ramakrishnan MA ; Raynor PC ; Tang W
-
Description:The aim of the work presented here is to study the effectiveness of building air handling units (AHUs) in serving as high volume sampling devices for airborne bacteria and viruses. An HVAC test facility constructed according to ASHRAE Standard 52.2-1999 was used for the controlled loading of HVAC filter media with aerosolized bacteria and virus. Nonpathogenic Bacillus subtilis var. niger was chosen as a surrogate for Bacillus anthracis. Three animal viruses; transmissible gastroenteritis virus (TGEV), avian pneumovirus (APV), and fowlpox virus were chosen as surrogates for three human viruses; SARS coronavirus, respiratory syncytial virus, and smallpox virus; respectively. These bacteria and viruses were nebulized in separate tests and injected into the test duct of the test facility upstream of a MERV 14 filter. SKC Biosamplers upstream and downstream of the test filter served as reference samplers. The collection efficiency of the filter media was calculated to be 96.5 - 1.5% for B. subtilis, however no collection efficiency was measured for the viruses as no live virus was ever recovered from the downstream samplers. Filter samples were cut from the test filter and eluted by hand-shaking. An extraction efficiency of 105 - 19% was calculated for B. subtilis. The viruses were extracted at much lower efficiencies (0.7-20%). Our results indicate that the airborne concentration of spore-forming bacteria in building AHUs may be determined by analyzing the material collected on HVAC filter media, however culture-based analytical techniques are impractical for virus recovery. Molecular-based identification techniques such as PCR could be used. [Description provided by NIOSH]
-
Subjects:
-
Keywords:
-
ISSN:1464-0325
-
Document Type:
-
Funding:
-
Genre:
-
Place as Subject:
-
CIO:
-
Topic:
-
Location:
-
Volume:8
-
Issue:10
-
NIOSHTIC Number:nn:20037361
-
Citation:J Environ Monit 2006 Sep; 8(10):1006-1013
-
Contact Point Address:James E. Farnsworth, Engineering Department, TSI Incorporated, 500 Cardigan Road, Saint Paul, MN 55126-3903
-
Federal Fiscal Year:2006
-
Performing Organization:University of Minnesota Twin Cities
-
Peer Reviewed:False
-
Start Date:20050701
-
Source Full Name:Journal of Environmental Monitoring
-
End Date:20250630
-
Collection(s):
-
Main Document Checksum:urn:sha-512:82bf914d7ea970f5fd2b5d2e84299b6734573b0979a8a89c39e5f4fa1bd6ad2bbe03a176832ff7fd8cbd325a86aa9a976f21047a934711933c386b845df4442c
-
Download URL:
-
File Type:
ON THIS PAGE
CDC STACKS serves as an archival repository of CDC-published products including
scientific findings,
journal articles, guidelines, recommendations, or other public health information authored or
co-authored by CDC or funded partners.
As a repository, CDC STACKS retains documents in their original published format to ensure public access to scientific information.
As a repository, CDC STACKS retains documents in their original published format to ensure public access to scientific information.
You May Also Like