i
52-Year-Old Electrical Technician Electrocuted in Indiana
-
1986/08/15
Details:
-
Corporate Authors:
-
Description:A 52 year old electrical technician, employed by a high voltage power transmission and distribution equipment company, was electrocuted while testing circuits. A metal cabinet containing a transformer, a capacitor, and two resistors had been repaired and sent to the quality assurance department for a final check. Electricity was being supplied to the electrical components in the cabinet from a variable output transformer. The technician determined that the rectifiers in the control circuit were shorted, replaced both rectifiers, and continued to follow the testing procedure check list. At the point where he was to measure the resistance of the two 5000 ohm resistors with an ohmmeter, he apparently reached into the metal cabinet with his left hand and attempted to remove one of the resistors. When he touched the resistor he was electrocuted. Recommendations arising from this accident include: a reevaluation of the testing procedure and check list for this task which would eliminate all unnecessary exposure to energized equipment; following the testing procedure check list and safe job procedure for repairing and testing a cabinet containing power transmission and distribution equipment; redesigning the variable output transformer so that it is controlled by one on/off switch; and designing power transmission and distribution equipment to incorporate safety considerations to protect workers who maintain, repair, and test these cabinets.
-
Content Notes:Publication date provided by the authoring office. There is no publication date indicated on the resource.
-
Subjects:
-
Keywords:
-
FACE - NIOSH and State:
-
Series:
-
Subseries:
-
DOI:
-
Publisher:
-
Document Type:
-
Genre:
-
Place as Subject:
-
CIO:
-
Division:
-
Topic:
-
Location:
-
Pages in Document:3 pages
-
NIOSHTIC Number:00170058
-
NTIS Accession Number:PB87-221727
-
Citation:Morgantown, WV: U.S. Department of Health and Human Services, Public Health Service, Centers for Disease Control, National Institute for Occupational Safety and Health, FACE 86-41, 1986 Aug; :1-6
-
Federal Fiscal Year:1986
-
Peer Reviewed:False
-
NAICS and SIC Codes:
-
Start Date:1986/07/21
-
Resource Number:FACE-86-41
-
Collection(s):
-
Main Document Checksum:
-
Download URL:
-
File Type: