i
Laborer Electrocuted in Ohio [FACE 87-11]
-
1986/12/15
Details:
-
Corporate Authors:
-
Description:An 18 year old laborer in an oil recycling plant was electrocuted when he contacted a pump casing that was energized due to faulty wiring. The victim was employed at a chemical service facility that recycles industrial and synthetic oils. He and a coworker were to pump the oil from a filtering tank into a kettle where it could be analyzed. The men were using a standard 7.5 horsepower, portable bane pump and a 2 inch, steel reinforced hose to accomplish this task. A short time after the pumping process was started, the victim was observed holding the pump with one hand and shaking; after 5 to 7 seconds he fell away from the pump. He was pronounced dead of electrocution. The portable pump frame was not grounded and the insulation on one of the conductors entering the motor connection box had been damaged, allowing a live conductor to become exposed which energized the metal pump frame. There was no strain relief device where the power cable entered the motor connection box. Without the strain relief device, any force exerted on the power cable could have contributed to the damaged conductor insulation. Recommendations arising from this accident were that electrical equipment be designed and maintained to comply with applicable requirements of the National Electrical Code, that the employer develop and implement formal safety training, and that the employer develop and implement a comprehensive preventive maintenance program for electrical equipment.
-
Content Notes:Publication date provided by the authoring office. There is no publication date indicated on the resource.
-
Subjects:
-
Keywords:
-
FACE - NIOSH and State:
-
Series:
-
Subseries:
-
DOI:
-
Publisher:
-
Document Type:
-
Genre:
-
Place as Subject:
-
CIO:
-
Division:
-
Topic:
-
Location:
-
NIOSHTIC Number:00174341
-
NTIS Accession Number:PB88-154810
-
Citation:Morgantown, WV: U.S. Department of Health and Human Services, Public Health Service, Centers for Disease Control, National Institute for Occupational Safety and Health, FACE 87-11, 1986 Dec; :1-5
-
Federal Fiscal Year:1987
-
Peer Reviewed:False
-
NAICS and SIC Codes:
-
Start Date:1986/11/04
-
Source Full Name:National Institute for Occupational Safety and Health
-
Collection(s):
-
Main Document Checksum:
-
Download URL:
-
File Type: