Welcome to CDC Stacks | A Fail-Safe Control System for a Mine Methane Pipeline - RI 8424 - 9632 | National Institute for Occupational Safety and Health
Stacks Logo
Advanced Search
Select up to three search categories and corresponding keywords using the fields to the right. Refer to the Help section for more detailed instructions.
 
 
Help
Clear All Simple Search
Advanced Search
A Fail-Safe Control System for a Mine Methane Pipeline - RI 8424
  • Published Date:
    1/1/1980
Filetype[PDF - 1.00 MB]


Details:
  • Description:
    The Bureau of Mines has designed and put into operation a fail-safe control system for use in underground coal mines equipped with methane drainage pipelines. This control system can detect certain unsafe conditions and respond by automatically shutting off the flow of methane from the degasification borehole to the drainage pipeline. Methane flow is shut off when the methane content in the return airways reaches a predetermined level (typically 1.5 pct), when the methane drainage pipeline is ruptured by roof fall, or when there is an electric power failure. The fail-safe control system was designed using commercially available components and a methane analyzer system previously developed by the Bureau. The fail-safe system consists of a unit that combines a shutoff valve and pneumatic valve actuator, and electronic and mechanical equipment designed to detect hazards and effect shutdown. The fail-safe control system was designed to meet regulatory requirements issued by the Mine Safety and Health Administration (MSHA), U.S. Department of Labor, and State regulatory bodies for the safe operation of underground methane pipelines used for mine degasification. MSHA has inspected and tested this system and permitted its use in two mines. The Bureau installed the fail-safe system in two working coal mines, where successful performance has been demonstrated.

  • Supporting Files:
    No Additional Files