Empirical determination of the error in the ACGIH method of predicting airflow distribution in two ventilation systems



Details

  • Personal Author:
  • Description:
    Ventilation systems are important in reducing worker exposure to airborne contaminants. To do this job sufficiently, ventilation systems must deliver the correct airflow to each hood according to its requirements. Proper airflow distribution is achieved through proper design, installation and maintenance. Proper design requires an accurate predictive model of the system. The most commonly used model is that described by the American Conference of Governmental Industrial Hygienists (ACGIH) in Industrial Ventilation: A Manual of Recommended Practice. The efficacy of this predictive model, which is based on published loss coefficients, has not been documented in the field and published literature. It is the purpose of this field study to compare the observed loss coefficients to those published by the ACGIH in the Industrial Ventilation manual. In this study, the error is determined by analyzing the differences between the observed sum of loss coefficients and the sum of published loss coefficients for each branch. Error in the loss coefficients is important because it results in a proportional error in airflow distribution. The data analysis for this work focused on the coefficients for different components (e.g. hoods, elbows) in an effort to identify the sources of deviation from the predicted sum of coefficients. That analysis indicated substantial discrepancies between the predicted and observed sums of loss coefficients which may translate into unacceptable shifts in airflow distribution. [Description provided by NIOSH]
  • Subjects:
  • Keywords:
  • Publisher:
  • Document Type:
  • Funding:
  • Genre:
  • Place as Subject:
  • CIO:
  • Topic:
  • Location:
  • Pages in Document:
    1-123
  • NIOSHTIC Number:
    nn:20045411
  • Citation:
    Seattle, WA: University of Washington, 1995 Jun; :1-123
  • Contact Point Address:
    Jeanne S. Hoppe, University of Washington, School of Public Health and Community Medicine, Department of Environmental Health, Room F226D, Box 357234, Seattle, WA 98195-7234
  • Federal Fiscal Year:
    1995
  • Performing Organization:
    University of Washington, Department of Environmental Health, Seattle, WA
  • Peer Reviewed:
    False
  • Start Date:
    19940401
  • Source Full Name:
    Empirical determination of the error in the ACGIH method of predicting airflow distribution in two ventilation systems
  • End Date:
    19971030
  • Collection(s):
  • Main Document Checksum:
    urn:sha-512:f313d422a5d4e15bb2c0eb14efbbe6c5e76b79d3cb178b6a3b8d87ed1b9595af6bb18c70abfb979eeb3cb39003c4afc07c6bf8b352707612e489f2dd1123b4c0
  • Download URL:
  • File Type:
    Filetype[PDF - 2.85 MB ]
ON THIS PAGE

CDC STACKS serves as an archival repository of CDC-published products including scientific findings, journal articles, guidelines, recommendations, or other public health information authored or co-authored by CDC or funded partners.

As a repository, CDC STACKS retains documents in their original published format to ensure public access to scientific information.