In-Depth Survey Report: Evaluation of Local Exhaust Ventilation System for Advanced Flat Sorter Machine at United States Postal Service, Baltimore Processing and Distribution Center, Baltimore, Maryland [2002-07]
Public Domain
-
2002/07/01
-
File Language:
English
Details
-
Personal Author:
-
Corporate Authors:
-
Description:Researchers from the National Institute for Occupational Safety and Health (NIOSH) conducted evaluations of an exhaust ventilation system developed for the Automated Flat Sorting Machine (AFSM) 100. This system was installed by the machines manufacturer to reduce the potential for employee exposure to harmful substances that could be contained in mailpieces processed by the machine. This effort is in response to recent terrorist attacks that used the mail as a delivery system for anthrax. NIOSH was asked to assist the United States Postal Service (USPS) in evaluating controls for this and other mail processing machinery. Evaluations were based on a variety of tests including tracer gas experiments, air velocity measurements, smoke release observations, and particle count experiments. The experiments showed that, overall, there is good capture by the exhaust ventilation system. Tracer gas tests indicated that the capture was essentially 100% between the feed table and the bucket insertion point. At the bucket insertion point, the measured capture efficiency was approximately 81%. The exhaust ventilation system also exhibited good capture characteristics based on smoke release experiments and air velocity measurements. Particle count measurements were inconclusive. It was determined that this method does not produce repeatable enough results for use in this situation. Based on these results and others discussed in this report, the following recommendations are suggested: 1. Consider adding a ventilated partial enclosure at the point where the mailpieces enter the moving buckets to reduce the potential for contaminant release
2. Seal cooling fan openings for fans that have been disconnected. These openings allow for the potential release of a substance that has been captured
3. Consider more thoroughly evaluating the capabilities of the exhaust system with additional smoke and tracer gas testing, particularly after changes are made to the ventilation and filtration system. The tested system only had ventilation on one of the three feeders, and HEPA filters were not installed on the filtration unit.
-
Subjects:
-
Keywords:
-
Series:
-
DOI:
-
Publisher:
-
Document Type:
-
Name as Subject:
-
Genre:
-
Place as Subject:
-
CIO:
-
Division:
-
Topic:
-
Location:
-
Pages in Document:1-15
-
Contributor:Maynard, Andrew ; Hoover, Mark
-
NIOSHTIC Number:nn:20035579
-
NTIS Accession Number:PB2009-113257
-
Citation:Cincinnati, OH: U.S. Department of Health and Human Services, Public Health Service, Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health, EPHB 279-12a, 2002 Jul ; :1-15
-
Federal Fiscal Year:2002
-
Peer Reviewed:False
-
NAICS and SIC Codes:
-
Collection(s):
-
Main Document Checksum:urn:sha-512:9af33bfffc093e37e07188e60b4d57b6a12a89af866502f399efd54a07a3b106e2eeb96c17f2c34e3d318165f47f184ed64e007d16bfd87f982dda5c8929daf9
-
Download URL:
-
File Type:
Related Documents
File Language:
English
ON THIS PAGE
CDC STACKS serves as an archival repository of CDC-published products including
scientific findings,
journal articles, guidelines, recommendations, or other public health information authored or
co-authored by CDC or funded partners.
As a repository, CDC STACKS retains documents in their original published format to ensure public access to scientific information.
As a repository, CDC STACKS retains documents in their original published format to ensure public access to scientific information.
You May Also Like