Evaluation of Indoor Environmental Quality in a Medical Office Building
Public Domain
-
2014/05/01
-
-
File Language:
English
Details
-
Personal Author:
-
Corporate Authors:
-
Description:The Health Hazard Evaluation Program received a request from employees at a medical office building. They were concerned about indoor environmental quality and exposure to sewer gas, specifically hydrogen sulfide. The medical office building was a four-story, concrete masonry office building constructed in the 1960s that had been renovated twice
the three main floors were converted into offices and exam rooms. The building was surrounded by manholes that had been identified as sources of odors. The building was within 30 feet of a 24-inch trunk line that carried sewage from approximately 60% of the surrounding area toward the wastewater treatment facility. Most of the building's current plumbing was the original cast iron waste and vent piping, which can become brittle and crack with age. We visited the facility in April 2013 and measured hydrogen sulfide, carbon dioxide, temperature, and humidity levels throughout the building. We also inspected the building's heating, ventilation, and air-conditioning system. We did not detect hydrogen sulfide in the building. We found that carbon dioxide concentrations generally increased when moving further away from the supply air discharge point on each floor
outdoor air supplied to each floor was not uniformly distributed. Temperature and humidity were within ANSI/ASHRAE recommended levels. We found problems with duct dampers, heat pumps, and the computerized control system, and determined that air flowed from the restrooms into the hallways. We found odor sources within and near the building such as dry drain traps and manholes. We recommended the employer improve the air quality in the building by (1) testing and balancing the heating, ventilation, and air-conditioning system, (2) increasing the amount of outdoor air coming into the building, and (3) fixing the problems with the duct dampers, heat pumps, and computerized control system. We also recommended the employer (1) remove plumbing fixtures and seal unused drain pipes, (2) replace cast-iron pipe with polyvinyl chloride pipe, and (3) create an employee and employer health and safety committee and hold regular meetings. We recommended employees (1) report odors to managers as soon as they occur, (2) not open building windows, and (3) participate in the health and safety committee. Following our visit, the employer reported that drain-trap devices were installed on all floor drains, HVAC components were inspected and repaired, cracks in the sanitary sewer lines were repaired, and manholes were sealed or replaced with solid lids and rain-guard devices. The employer reported that odor complaints have decreased since our evaluation.
-
Subjects:
-
Keywords:
-
Source:Cincinnati, OH: U.S. Department of Health and Human Services, Public Health Service, Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health, HETA 2012-0266-3210, 2014 May ; :1-17 ; Cincinnati, OH: U.S. Department of Health and Human Services, Public Health Service, Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health, HETA 2012-0266-3210, 2014 May ; :1-17
-
Series:
-
Subseries:
-
DOI:
-
Publisher:
-
Document Type:
-
Genre:
-
Place as Subject:
-
CIO:
-
Division:
-
Topic:
-
Location:
-
Pages in Document:24 pdf pages
-
Contributor:Booher, Donald E. ; El Burai-Felix, Alia ; Galloway, Ellen ; Hartle, Greg ; Watts, Shawna
-
NIOSHTIC Number:nn:20044396
-
NTIS Accession Number:PB2014-106314
-
Citation:NIOSH [2014]. Health hazard evaluation report: evaluation of indoor environmental ; quality in an office building. By Oza A, Methner M. Cincinnati, OH: U.S. Department ; of Health and Human Services, Centers for Disease Control and Prevention, National ; Institute for Occupational Safety and Health, NIOSH HHE Report No. 2012-0266- ; 3210,
-
CAS Registry Number:
-
Federal Fiscal Year:2014
-
NORA Priority Area:
-
Peer Reviewed:False
-
NAICS and SIC Codes:
-
Collection(s):
-
Main Document Checksum:urn:sha-512:4cd62d87cb01224c50080db3928205763b4d4cfccb1e24bbdfabe665e6ea9810e8c50cfad9758440db34282d5ad10072c29da17302bc265437a59dd111f88368
-
Download URL:
-
File Type:
File Language:
English
ON THIS PAGE
CDC STACKS serves as an archival repository of CDC-published products including
scientific findings,
journal articles, guidelines, recommendations, or other public health information authored or
co-authored by CDC or funded partners.
As a repository, CDC STACKS retains documents in their original published format to ensure public access to scientific information.
As a repository, CDC STACKS retains documents in their original published format to ensure public access to scientific information.
You May Also Like