Health Hazard Evaluation Report: HETA-88-364-2103: Library of Congress, Madison Building, Vol. II; Results of Indoor Air Environmental Monitoring, Washington, D.C.
-
1990/07/01
Details:
-
Corporate Authors:
-
Description:A systematic study was designed to assess the nature and spatial distribution of employee health symptoms and comfort concerns in the Madison Building of the Library of Congress (LOC), Washington, DC. Environmental monitoring was conducted at more than 100 sites within the building. The mean temperature for the building was 73.1 degrees-F, with a general trend for the temperature to increase throughout the building on all days from morning to afternoon. The mean relative humidity was 49.2%. Mean carbon-dioxide (124389) measurements increased at all sampling locations throughout the morning. Whole building air exchanges were relatively constant averaging between 0.85 and 0.79 air changes per hour. The real time respirable particle measurement mean value was 5.5 micrograms/cubic meter (microg/m3). Nicotine (54115) was detected in several areas of the building ranging as high as 18.5microg/m3. Formaldehyde (50000) concentration was very low as was the acetaldehyde (75070) concentration. The mean acetone (67641) concentration was 32.5microg/m3. Volatile organic compounds ranged as high as 2ppm with the most predominant ones being xylene (1330207). The mean benzene (71432) concentration was 2 parts per billion. Total volatile organic compounds averaged 1.1 parts per million (ppm). Chlorpyrifos (2921882) was the only targeted pesticide observed above the analytical limit of detection and was documented in only one sample at 0.004microg/m3. Whole building carbon-monoxide (630080) (CO) levels averaged between 1 and 2ppm.
-
Subjects:
-
Keywords:
-
Series:
-
Subseries:
-
DOI:
-
Publisher:
-
Document Type:
-
Genre:
-
Place as Subject:
-
CIO:
-
Division:
-
Topic:
-
Location:
-
Pages in Document:245 pdf pages
-
Contributor:Fine, Lawrence; Teichman, Kevin; Candall, Michael; Gorman, Richard; Stanevich, Rebecca; Burr, Gregory A.; Seitz, Teresa A.; Burroughs, G. E.; Klein, Matthew K.; Kennedy, Eugene; Highsmith, Ross; Wallace, Lance; Lumpkin, Tom; Hern, Steve; Thompson, Vinson; McLauchlin, Ken; Stetzenbach, Linda; Leaderer, Brian; Selfridge, Oliver John; Persily, Andrew; Fidler, Anne; Wilcox, Thomas; Hurrell, Joseph; Hornung, Richard; Kollander, Mel; Brenner, F. Cecil; Clickner, Robert; Dietz, Stephen; Nelson, C. J.
-
NIOSHTIC Number:00200828
-
NTIS Accession Number:PB92-103183
-
Citation:Cincinnati, Ohio: U.S. Department of Health and Human Services, Public Health Service, Centers for Disease Control, National Institute for Occupational Safety and Health, HETA 88-364-2103, 1990 Jul; :1-265
-
CAS Registry Number:
-
Federal Fiscal Year:1990
-