CDC STACKS serves as an archival repository of CDC-published products including scientific findings, journal articles, guidelines, recommendations, or other public health information authored or co-authored by CDC or funded partners.
As a repository, CDC STACKS retains documents in their original published format to ensure public access to scientific information.
i
23-Year-Old Lineman Electrocuted in North Carolina
-
1986/04/21
Details:
-
Corporate Authors:
-
Description:A 23 year old lineman was electrocuted when he came into contact with a lightning arrestor conductor during work on a connection box on a utility pole. The lineman and a supervising lineman were to remove and replace a capacitor bank from a utility pole in a rural area. The upper cross member supported three 7200 volt conductors and each conductor had attached to it a lightning arrestor. The victim was inside a one person aerial bucket 25 feet above the ground. Protective insulating hoses were placed over two of the primary conductors. However, the lightning arrestor conductors attached to the primary conductors prevented the hoses from slipping all the way to the cross member on the utility pole. The victim used no boots, blankets, or other insulating material to cover the lightning arrestor conductors or other live conductors. He did not use his insulated rubber gloves. Evidence indicated that the victim was holding the wire cable with his left hand when his right hand came in contact with the lightning arrestor conductor. The cause of death was cardiac arrest due to contact with 7200 volts of electricity. Recommendation include: use of appropriate protective equipment including insulating boots, blankets and hoses when working with electricity; assessment of the effectiveness of corporate safety management and the comprehensive corporate safety program; and proper training in hazard recognition, safe work practices and emergency response for all personnel upon hiring.
-
Content Notes:Publication date provided by the authoring office. There is no publication date indicated on the resource.
-
Subjects:
-
Keywords:
-
FACE - NIOSH and State:
-
Series:
-
Subseries:
-
DOI:
-
Publisher:
-
Document Type:
-
Genre:
-
Place as Subject:
-
CIO:
-
Division:
-
Topic:
-
Location:
-
Pages in Document:4 pages
-
NIOSHTIC Number:00170042
-
NTIS Accession Number:PB87-223285
-
Citation:Morgantown, WV: U.S. Department of Health and Human Services, Public Health Service, Centers for Disease Control, National Institute for Occupational Safety and Health, FACE 86-20, 1986 Apr; :1-9
-
Federal Fiscal Year:1986
-
Peer Reviewed:False
-
NAICS and SIC Codes:
-
Start Date:1986/03/21
-
Resource Number:FACE-86-20
-
Collection(s):
-
Main Document Checksum:
-
Download URL:
-
File Type: