On September 16, 2019, a 68-year-old captain was killed in a propane explosion and six firefighters were injured. At approximately 0808 hours, the fire and rescue department was dispatched to an office building for a possible propane leak. The building maintenance supervisor had called the fire station directly. The fire chief called county dispatch, so the call could be transmitted by radio to the fire and rescue department. County dispatch alerted Car 1, Engine 2, and Tower 3 at 0808 hours. The fire chief (Car 1) arrived on-scene and met with the building maintenance supervisor. The employees had moved to their designated evacuation area, which was the northwest corner of the parking lot. Firefighters from Engine 2 and Tower 3 arrived on-scene. The officer and firefighter from Tower 3 initiated air sampling with a portable multi-gas detector. Tower 3 members conducted air sampling around the propane tank. They found no indication of a propane leak, but the propane tank was empty with frost on the bottom half of the tank and the ground around the tank at approximately 0813 hours. Firefighters were ordered to the basement of the building by the fire chief. The fire chief and a captain who responded on Engine 2 were reportedly on the 1st floor of the building. A firefighter assigned to Tower 3 went to the basement with a portable multi-gas detector. The captain from Tower 3 was already in the basement with the building maintenance supervisor and a firefighter from Engine 2. The firefighter from Tower 3 stated that the multi-gas detector started to read a lower explosive limit (LEL) as he went down the basement stairs. The LEL continued to increase until the multi-gas detector alarmed at 100% at the bottom of the steps. The firefighter from Tower 3 stated he was in the basement less than one minute. At 0817 hours, an explosion occurred that leveled the building. The captain of Engine 2, who was reportedly on the 1st floor, was killed as a result of injuries sustained in the explosion. Two firefighters were standing on Side Bravo in the parking lot when the explosion occurred. The force of the explosion threw them to the dirt road approximately 20-30 feet away. Six firefighters, including the fire chief, and the building maintenance supervisor were injured. Initially, all six injured firefighters were transported to a local hospital. One firefighter was treated and released. The other five firefighters were transported by air or ground to various hospitals throughout the state. The captain of Engine 2 was pronounced deceased by EMS personnel at approximately 0840 hours. Key Recommendations: 1) Fire departments responding to a hazardous materials incident should ensure that a scene size-up and initial risk assessment are performed. In addition, fire departments should establish isolation zones and ensure a continuous risk assessment is conducted throughout the incident 2) Fire departments should ensure incident commanders initiate a defensive strategy and communicates the incident action plan (tactics) during initial operations of a hazardous materials incident. The strategy and incident action plan are revised based upon the tactical objectives taken to mitigate the hazard 3) Fire departments should ensure firefighters are trained to understand the scrubbing or odorant fade of ethyl mercaptan from propane. This training includes the use of multi-gas detectors to determine if a potentially explosive atmosphere is present.
-
Subjects:
-
Keywords:
-
FACE - Firefighter:
-
Series:
-
Subseries:
-
DOI:
-
Publisher:
-
Document Type:
-
Genre:
-
Place as Subject:
-
CIO:
-
Division:
-
Topic:
-
Location:
-
Pages in Document:1-71
-
Contributor:Hundley, Mark ; Okonski, Kevin
-
NIOSHTIC Number:nn:20064694
-
Citation:Morgantown, WV: U.S. Department of Health and Human Services, Public Health Service, Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health, FACE F2019-16, 2022 Jan ; :1-71
-
CAS Registry Number:
-
Federal Fiscal Year:2022
-
NORA Priority Area:
-
Peer Reviewed:False
-
NAICS and SIC Codes:
-
Start Date:2019/09/16
-
Collection(s):
-
Main Document Checksum:urn:sha-512:cde3092736bcf99da7b96cc194d532bab51fd4cceb603c3bf1d9e2636d81fde1368bb8991ad59df4e342dbe9763ebacd898ce0a771a3be0466d1e13188057060
-
Download URL:
-
File Type:
Supporting Files
File Language:
English
ON THIS PAGE
CDC STACKS serves as an archival repository of CDC-published products including
scientific findings,
journal articles, guidelines, recommendations, or other public health information authored or
co-authored by CDC or funded partners.
As a repository, CDC STACKS retains documents in their original published format to ensure public access to scientific information.
As a repository, CDC STACKS retains documents in their original published format to ensure public access to scientific information.
You May Also Like