Evaluation Of Iyoni II Methanometers
-
2003
Source: 30th International Conference of Safety in Mines Research Institutes. Johannesburg, Republic of South Africa: South African Institute of Mining and Metallurgy, 2003 Oct; :579-594
Details:
-
Personal Author:
-
Corporate Authors:
-
Conference Authors:
-
Description:No regular monitoring of methane is required in areas of gassy coal mines outby the mining face. Methane ignitions that have occurred in mine outby areas indicate the need to provide better protection to workers. Handheld methane monitors are now used by some miners to make periodic measurements of methane at the working face. The IYONI II gas detector which is incorporated into a miner’s cap lamp and worn on a miner’s helmet can continuously provide an alarm signal whenever methane levels exceed a set level. Tests were conducted to evaluate the performance characteristics of this methane detector by measuring response times with methane gas supplied through a calibration fixture or adaptor. Other response time tests were performed with the detector in an environmental test box. Performance was also evaluated in a full scale test gallery where face methane emission and underground ventilation were simulated. Procedures for calibration by response time measurement of the IYONI II detector have been developed. In limited testing, the IYONI II detector was found to reliably detect the presence of 1 percent by volume methane.
-