i
Thermal and electrical ignitability of dust clouds
Details:
-
Personal Author:
-
Corporate Authors:
-
Description:"The Bureau of Mines conducted a comprehensive laboratory study of the thermal ignitability of various carbonaceous dust clouds with particular emphasis on various ranks of coal dust. The tests were conducted using a new 1.2-L furnace. Autoignition temperatures of dust clouds were obtained as a function of coal volatility and particle size. Dust particles and gas samples were collected by a rapid-sampling system in order to study the reactions involved in preignition and postignition processes. The autoignition temperatures measured in the new 1.2-L furnace were significantly lower and therefore more conservative than those measured previously in the Godbert-Greenwald furnace. The combined effects of thermal and electrical ignition of dust clouds were also studied in the 1.2- L furnace using electrical discharges of varying energies at ambient and elevated temperatures. The minimum spark energy necessary to ignite a dust cloud decreased significantly as the temperature of the dust cloud increased." - NIOSHTIC-2
NIOSH no. 10003092
-
Subjects:
-
Document Type:
-
Collection(s):
-
Main Document Checksum:
-
Download URL:
-
File Type:
Supporting Files
-
No Additional Files
More +